Key Features
- Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance or water adding
- Not restricted for air transport-complies with IATA/ICAO Special Provision A67
- UL-recognized component
- Can be mounted in any orientation
- Computer designed lead, calcium tin alloy grid for high power density
- Long services life, float or cyclic applications
- Maintenance-free operation
- Low self discharge
- Case and cover available in both standard and flame retardant ABS
Technical Specifications
| Performance Characteristics – Model | ORC12-150CT |
|---|---|
| Performance Characteristics – Nominal Voltage | 12 V |
| Performance Characteristics – Number of Cells | 6 |
| Performance Characteristics – Design Life | 10 years |
| Nominal Capacity – 10 hour rate (20 A, 10.8 V) | 150 Ah |
| Nominal Capacity – 5 hour rate (34.7 A, 10.5 V) | 136 Ah |
| Nominal Capacity – 1 hour rate (129 A, 9.6 V) | 110 Ah |
| Performance Characteristics – Internal Resistance | Fully charged battery 77°F (25°C) Self-Discharge ≤ 4.5 milli Ω |
| Performance Characteristics – Discharge | -20~60°C |
| Performance Characteristics – Charge | -10~60°C |
| Performance Characteristics – Storage | -20~60°C |
| Performance Characteristics – Maximum Discharge Current 77°F (25°C) | 1050(5s) |
| Performance Characteristics – Short Circuit Current | 2680A |
| Charge Methods – Cycle Use | 2.40-2.45 VPC |
| Charge Methods – Maximum Charging Current | 45A |
| Charge Methods – Temperature Compensation | -30 mV/°C |
| Charge Methods – Standby Use | 2.20-2.28 VPC |
| Charge Methods – Temperature Compensation | -20 mV/°C |








Reviews